A cold room floor has to limit heat gain while carrying the loads from daily operations. When comparing insulation quotes, ask what each square metre includes, which loads the floor was designed for, and what the team can still inspect before the layers are covered.
Start With the Floor Section and Actual Loads
Give the designer the target room temperature, the latest floor section and the intended use. For pallet racking, ask the rack supplier for the layout, maximum reactions at individual feet and baseplate sizes. For forklifts, provide the loaded wheel loads and typical routes, including turns and crossings. Total truck weight or average load per square metre alone does not describe how the floor is loaded.
A rack foot concentrates load at one location and may apply it for long periods. Forklift wheels apply moving, repeated loads. The CEBA-IARW warehouse design guide, Chapter 5, §5.1.1 distinguishes those load cases. How the slab or wearing layer spreads the loads into the insulation and supporting structure depends on the complete floor design, including its joints and supports.
Read Two Compression Values, Not Just One
Ask for the technical data and declaration for the exact board and thickness offered. Compare declared thermal conductivity or thermal resistance for the selected thickness, then check these two different mechanical properties:
- Short-term compression: A laboratory result for how the board responds to compression in a short test, often reported at 10% deformation or as compressive strength. It is not a load that a finished floor can safely carry.
- Compressive creep: How much the board deforms over time under sustained stress. Look for the declared stress, deformation limits and assessment period rather than assuming the short-term figure applies to long-term loading.
ISO publishes separate test methods for compression behaviour and compressive creep. As an example of reading a declaration, one manufacturer's XPS declaration, page 1 under EN 13164 lists CS(10/Y)500 and CC(2/1.5/50)180. The 500 kPa is the short-term compression class. The 180 kPa is the declared sustained stress for the 50-year creep designation, with limits of 2% total thickness reduction and 1.5% creep deformation, based on extrapolated test results. Neither number is a design capacity for your floor, and the example is not a product recommendation.
Put Both Quotes on the Same Square-Metre Basis
Suppose a room has 100 m² of finished floor and three insulation layers, each laid over the full area. The net board coverage is 300 m² before cutting waste and order rounding. The finished floor is still 100 m². This is a quantity example, not a recommendation to use three layers.
Ask each bidder to state whether their rate is per square metre of board coverage or completed floor. Request the total insulation thickness and each layer's material, thickness and quantity. Check whether the quote includes cutting waste, perimeter detailing, the vapour retarder, the wearing slab and installation. Compare like for like before comparing rates.
Check the Details Before They Are Covered
Water absorption and water-vapour resistance describe different properties; low board water absorption does not establish that the floor assembly controls water vapour. ASHRAE's refrigerated-facility design chapter explains why the vapour retarder must remain continuous between adjoining surfaces, including walls and floors.
Before covering the work, check the board identification, layer thicknesses, board joints and vapour-retarder connections against the approved detail. Look closely at wall–floor junctions, thresholds and penetrations. Record the locations with photos if that forms part of the site's inspection process. The correct layer sequence and tie-ins depend on the project drawings. For frost heave, suspended slabs and floor sensors, see Does a Cold Room Need Underfloor Heating?.
What to Send for a Project Review
Share your latest floor section, target room temperature, rack layout and maximum foot reactions, and loaded forklift wheel loads and routes with the design team. For a cold room project in Singapore, contact Airnovation with these details so we can discuss the insulation scope and the information needed for a project-specific review.